If the SubDrive/MonoDrive Connect displays F1, it signals a motor underload fault. The motor is drawing less current (amperage) than the minimum parameter setting.
|
Possible Causes |
Corrective Actions |
|
Damaged pump |
Repair or replace pump and motor assembly as needed. |
|
Plugged screen |
Remove debris from pump screen. |
|
Invalid DIP switch selection for pump end HP (on new installs) |
Verify DIP switches are set properly. |
|
System is drawing down to pump inlet (out of water); over-pumped well; well is running dry |
If not out of water, check the underload sensitivity setting. |
|
High static, light loading pump |
|
|
Frequency near maximum, with load less than configured underload sensitivity |
|
|
Incorrect/backwards motor rotation |
Check pump rotation (SubDrive and three-phase motor only). Reconnect if necessary for proper rotation. |
|
Air/gas locked pump |
If possible, set deeper in well to reduce possibility of air/ gas locked pump. |
|
Maximum frequency set too low for permanent magnet motor |
For MagForce™ motor, increase maximum frequency to 125Hz or more for - if maximum frequency must be below 125Hz, adjust underload sensitivity setting to a lower value. |
If the SubDrive/MonoDrive Connect displays F2, it signals an undervoltage fault. The voltage provided to the drive unit is measured to be less than 180 VAC. The measurement is between the L1 and L2 terminals at the incoming power connection terminals.
|
Possible Causes |
Corrective Actions |
|
Low incoming voltage measured at the drive terminals |
The line voltage needs to be 190 to 260 VAC. Correct incoming voltage. Contact the power company. |
|
Mis-wired input leads |
Check incoming power connections and correct or tighten if necessary. |
|
Loose connection at breaker or panel |
Check circuit breaker or fuses. |
|
Possible internal drive issue |
If above measurements and corrections are made with no resolution, replace drive. |
NOTE: Refer to the owner’s manual for more information.
If the SubDrive/MonoDrive Connect displays F3, it signals an overcurrent or locked pump fault. If the motor current is higher than the maximum load or service factor amperage of the motor, then the drive tries to lower the speed to bring the current below the limit while lowering the speed below a certain frequency. If the overcurrent is still active, the drive declares F3.
|
Possible Causes |
Corrective Actions |
|
Motor and/or pump misalignment |
Remove and repair or replace as required |
|
Dragging motor and/or pump |
|
|
Motor and/or pump locked |
|
|
Abrasives in pump |
|
|
Open phase on 3 wire motor with long leads |
|
|
Excess motor cable length |
Reduce motor cable length. Adhere to Maximum Motor Cable Length table in the owner’s manual. |
|
Amperage above motor maximum load or service factor level at 30 Hz |
Confirm correct setting for pump and motor and inspect pump for motor for mechanical interference. |
|
Incorrect motor selection during drive DIP switch programming. |
Confirm the motor type on DIP SW1 Position 7 is set correctly. Confirm the motor HP on DIP SW2 Positions 1-6. |
NOTE: Refer to the owner’s manual for more information.
If the SubDrive/MonoDrive Connect displays F5, it signals an output open phase fault. The drive is seeing little or no current on one or more motor leads. If no current or low current is detected in one of the motor phases, then F5 will be declared.
|
Possible Causes |
Corrective Actions |
|
Loose connection anywhere in the motor cable or directly to the drive |
· Check the drop cable and motor resistance, tighten output connections, and repair or replace as necessary. · Use dry motor to check drive functions. If drive runs and exhibits an underload fault, drive is good. · Perform a megger test at the motor lead on the drive end. · IMPORTANT: Make sure to disconnect the lead from the VFD before testing. |
|
Defective motor or drop cable (disconnected cable) |
|
|
Motor phase and horsepower do not match the drive settings. |
· Confirm the motor phase DIP SW1 Position 2, and motor HP on DIP SW2. · Confirm motor settings match the motor being used. |
NOTE: Refer to the owner’s manual for more information.
If the SubDrive/MonoDrive Connect displays F6, it signals a short circuit fault. Any short between the motor leads is detected as an F6 fault.
|
Possible Causes |
Corrective Actions |
|
Phase to phase short |
· Check the drop cable and motor resistance. Perform a megger test at the motor leads on the drive end. IMPORTANT: Make sure to disconnect the lead from the VFD before testing. · Fix wiring as necessary. If fault is present after resetting and removing motor leads, replace the drive. |
|
Phase to ground short |
NOTE: Refer to the owner’s manual for more information.
If the SubDrive/MonoDrive Connect displays F27, it signals a pressure transducer error. The 4-20 mA signal received from transducer is not within range.
|
Possible Causes |
Corrective Actions |
|
Pressure transducer has failed |
Replace pressure transducer |
|
Pressure transducer is incorrectly wired |
Check pressure transducer wiring connections |
|
Pressure transducer is in use but the DIP switch selection for the type of sensor input is incorrect |
Ensure DIP SW1 Position 5 is in the correct position for the sensor type being used: DOWN for pressure transducer, UP for pressure switch. |
NOTE: Refer to the owner’s manual for more information.

The plastic bushing on the pressure transducer on the SubDrive/MonoDrive Connect is an isolator. It was added after Franklin Electric upgraded the part for several SubDrive products to provide improved surge performance.
The configuration of a Franklin Electric transducer is slightly different from other suppliers. If purchasing a transducer from another supplier, keep the following in mind:
NOTE: The Sensata + Isolator pressure transducer solution has been the standard offering with SubDrive Utility “XD” models since product launch (September 2021)
When using the transducer, the SubDrive Constant pressure controller allows for more programming functions:
|
Function |
Transducer |
Pressure Sensor |
|
Voltage (VDC) |
24 |
Pulsed signal |
|
Pressure Measurement (psi) |
Up to 200* |
Up to 150** |
|
Max distance from SubDrive (ft) |
200 |
100 |
|
Drawdown |
Yes |
No |
|
Overpressure Setpoint |
||
|
Proportional Gain |
||
|
Integration Time |
||
|
Bump Mode |
Pressure Bump Level, Bump Timeout, Delay to Sleep |
Off, Standard, Aggressive Large Tank/Small Tank |
|
Pressure Adjustment Location |
At SubDrive unit |
At Sensor |
|
Pressure Adjustable through FE Connect App |
Yes |
No |
NOTE: *SubDrive Connect models come with a 100 psi transducer. Franklin Electric offers accessories for up to 200 psi.
NOTE: **SubDrive Connect models do not come standard with the pressure sensor. Franklin Electric offers two kits with a pressure sensor. One kit has a max rating of 90 psi, and the other has a max rating of 150 psi.
Yes, the current SubDrive Connect design includes enhanced electrical noise filtering. Read more in this news article and/or in this technical bulletin.
The SubDrive Connect is suitable for outdoor use with a NEMA 3R rating; however, the following considerations should be made for outdoor installations:
NOTE: Refer to the owner’s manual for more information.
Yes, the display is a replaceable item. You will need to know the serial number or date code to confirm correct replacement part. Click here for a complete list of available parts.
Yes, Franklin Electric has a surge arrestor to protect against lightning: part number 150814902.
Franklin Electric has optimized the SubDrive Connect Variable Frequency Drive for use with all Franklin Electric products. Using the Franklin Electric SubDrive with non-Franklin Electric products may result in suboptimal performance.
All faults are recorded in a log file for review during troubleshooting activities. Some faults may be temporary, allowing the drive to restart after a timeout period. However, certain faults can cause the SubDrive to cease operation of the pump and motor. In such cases, the SubDrive can be powered off, and after a few minutes, powered back on. The SubDrive will attempt to restart the pump and motor, but the initial fault condition may cause the unit to return to a ceased operation state. If this happens, further troubleshooting specific to the fault code being shown may be required.
Yes. A factory reset can be completed through the FE Connect App or manually on the drive. To reset manually on the drive:
Consult your Franklin Electric water well professional for advice on firmware updates. Refer to the Firmware Release Notes.
When the SubDrive/MonoDrive Connect NEMA 4 detects that water is being used, the drive starts and increases the motor speed slowly, gradually increasing voltage, resulting in a cooler motor and lower start-up current compared to conventional water systems.
NOTE: Two-wire motors do not have soft start ability.
Follow local codes and standards. Franklin Electric does not recommend using a Ground Fault Circuit Interrupter (GFCI) and/or an Arc-Fault Circuit Interrupter (AFCI). Use of a GFCI and/or an AFCI may cause nuisance trips.
Franklin Electric is a global leader in the production and marketing of systems and components for the movement of water and energy. Recognized as a technical leader in its products and services, Franklin Electric serves customers worldwide in residential, commercial, agricultural, industrial, municipal, and fueling applications. Franklin Electric is proud to be recognized in Newsweek’s lists of America’s Most Responsible Companies 2024, Most Trustworthy Companies 2024, and Greenest Companies 2025; Best Places to Work in Indiana 2024; and America’s Climate Leaders 2024 by USA Today.