Standard Pump Soft Starter

Standard Pump Soft Starter

3Ø, 50/60 Hz, 200~600 VAC, 2~75 HP
Integrated electronic overload
Wide-range voltage acceptance (200~600 VAC)
HP Rated Contactor Bypass

IQ Logo

FE Select - Configure & Quote

U.S.A. Canada
Features
Order Info
Specs & Accessories
Downloads
  • Electronic motor protection and automation I/O

    • Wide-range, class 10 electronic overload
    • Current phase unbalance protection
    • Locked rotor / stall protection
    • Cycle fault protection
    • Accepts 200-600 VAC directly, true plug and play
    • Voltage auto-run input
    • Dry contact auto-run input
    • Status relay output
    • Hand/Off/Auto keypad with LEDs for mode, fault and run indication

    Soft starter features

    • Full HP rated bypass contactor
    • Across-the-line start for emergency situations
    • Adjustable current limit, start/stop voltage, and
    • start/stop time
    • SCR over-temperature detection
    • Shorted SCR detection

    Optional circuit breaker disconnect (Service Entrance rated)

    • UL 489 circuit breaker provides branch and short circuit protection
    • No fuses required – saves time and money
    • Lockable handle for safety

    Industrial grade construction

    • Door mounted HOA keypad
    • Housed in an outdoor rated, gasketed, NEMA 3R enclosure
    • NEMA rated bypass contactor features 2.5 million electrical cycles at full rated current - nearly twice the life as our competitors
  • With Service Entrance Circuit Breaker Disconnect

    Part Number200 V - 460 V
    3-Phase SFA
    Range** (A)
    600 V
    3-Phase SFA
    Range** (A)
    3-PHASE HP (UL) / Max. SFA**Contactor
    NEMA Size
    200 V230 V460 V600 V
    HPSFAHPSFAHPSFAHPSFA
    SPS3R-RV-S1-J-G156~86~8282858581
    SPS3R-RV-S1-J-G208~118~113113117.5111011
    SPS3R-RV-S1-J-G3011~1711~1731751710171517
    SPS3R-RV-S1-J-G4016~2216~225227.52215222022
    SPS3R-RV-S1P-J-G5020~2820~287.5281028202825281+
    SPS3R-RV-S1P-J-G6024~3424~321034103425343032
    SPS3R-RV-S2-J-G8032~4532~4510451545304540452
    SPS3R-RV-S3-J-G10040~5740~5715572057405750573
    SPS3R-RV-S3-J-G12550~7150~712071257150716071
    SPS3R-RV-S3P-J-G15060~8560~7725853085608575773+
    • Standard Pump Soft Starter - 3-Phase, 50/60 Hz, 200~600 VAC
    • NEMA Type 3R Enclosed - Combination Soft Starter
    • Includes Service Entrance Circuit Breaker Disconnect

    Disconnect not Included

    Part Number200 V - 460 V
    3-Phase SFA
    Range** (A)
    600 V
    3-Phase SFA
    Range** (A)
    3-PHASE HP (UL) / Max. SFA**Contactor
    NEMA Size
    200 V230 V460 V600 V
    HPSFAHPSFAHPSFAHPSFA
    SPS3R-RV-S00-J1~DPV*1~927.82957.67.590
    SPS3R-RV-S0-J6~DPV*6~17517.5518101415170
    SPS3R-RV-S1-J10~DPV*10~277.525.31028202725271
    SPS3R-RV-S1P-J20~4020~3210401040304030321+
    SPS3R-RV-S2-J30~5030~5015501550305040502
    SPS3R-RV-S3P-J45~8545~7725853085608575773+
    • Standard Pump Soft Starter - 3-Phase, 50/60 Hz, 200~600 VAC
    • NEMA Type 3R Enclosed - Standard Soft Starter
    • Disconnect not Included

    Factory Installable Options

    Part NumberDescription
    SPS-SRG240Surge Suppressor, 200/230 V
    SPS-SRG480Surge Suppressor, 460 V
    SPS-SRG600Surge Suppressor, 600 V

    Dimensions

    Standard Pump
    Soft Starter
    Starter
    Type
    HeightWidthDepth
    SPS3R-RV-S1-J-GXXCombination221510
    SPS3R-RV-S1P-J-GXXCombination
    SPS3R-RV-S2-J-GXXCombination
    SPS3R-RV-S3-J-GXXXCombination321510
    SPS3R-RV-S3P-J-GXXXCombination
    SPS3R-RV-S00-JStandard221510
    SPS3R-RV-S0-JStandard
    SPS3R-RV-S1-JStandard
    SPS3R-RV-S1P-JStandard
    SPS3R-RV-S2-JStandard
    SPS3R-RV-S3P-JStandard321510
  • Soft Starter Type
    SPS-RV - Standard Pump Soft Starter
    Standard or Combination (Service Rated, Suitable for use as a Service Disconnect)
    NEMA Type 3R Enclosed
    User Interface
    Settings AdjustmentsInternal
    Hand-Off-Auto Door mounted keypad
    Standard Control Operations
    InputsVoltage AutoAccepts 12-250VAC/DC. Applying voltage will send a run command to the starter when in Auto mode.
    Dry Contact Auto Normally Open dry contact. When closed, the starter will be commanded to run when in Auto mode.
    OutputStatus RelayNormally Open relay contact, 0.3A @ 125VAC, 1A @ 24VAC
    OperationalOverload TypeElectronic, I2t trip curve
    Power FailRestart in last mode (Hand/Off/Auto) with no delay (default)
    Fault ResetAdjustable: Manual (default) or Automatic
    Starts6/hour, 20 seconds max. start time @ 400% FLA, 30 seconds max. start time @ 300% FLA
    Environmental
    Ambient Operating Temp-5° to 140° F (-20° to 60° C)
    Ambient Storage Temp-5° to 185° F (-20° to 85° C)
    Relative Humidity5% to 95% non-condensing
    Motor / Soft Starter ProtectionAdjustment / DescriptionDefault Setting
    Overload Current Setting RangeDiffers per modelPer SFA
    Overload Trip Class1010
    Cycle FaultAlways On: Trip if cycle rate exceeds 20 starts/minuteOn
    Current Phase UnbalanceAlways On: Trips in the event of a current phase unbalance greater than 50%On
    Locked Rotor / StallAlways On: Trips within 0.5 secondsOn
    Shorted SCRAlways On: Trips upon detection of a shorted SCR or no motorOn
    Open SCRAlways On: Trips if no current is detected during start-up or bypassOn
    SCR Over-TemperatureAlways On: Trips if the SCR temperature reaches 125oCOn
    Across-the-Line StartOn/Off: Allows the user to start the motor across-the-lineOff